No fire rated box systems, or listed insulation matting systems, nor gypsum layer assembies, have been tested for use with MI cable terminations. Use of these systems for MI cable splicing may affect the performance of the cable, and will affect the UL system listing of the MI cable. These boxes, and or, assemblies often carry their own fire ratings, and therefore that section of the MI wire system's performance, will be reliant on the box, or assembly listing, of that vendor, and not nVent Thermal Management. It is recommended that use of these assemblies in a MI fire rated wiring system, be reviewed by nVent Thermal Management and the AHJ involved.