3SC-LTC

Overview

The nVent RAYCHEM 3SC-LTC is a below insulation end seal kit for use with RAYCHEM 3SC60, 3SC70 and 3SC80 electric heat trace cable in longline heating applications. It is approved by CSA and FM for use in hazardous locations. This RAYCHEM termination kit may be installed at temperatures as low as –40°F (–40°C). For easier installation, store the RAYCHEM 3SC-LTC end termination kit above freezing until just before installation.

Industries Served:
Chemical and Pharmaceutical
Food and Beverage
Marine
Mining
Oil and Gas
Power

Technical Specifications

  1. The connection kit shall be constructed of copper free aluminum NEMA 4 rated enclosure with epoxy finish and should fit below a 2 inch insulation.
  2. The connection mechanism shall be high temperature soldered crimps for reliable and long-term good electrical contact
  3. The connection kit should be sealed with potting compound rated for 250°C continuous exposure temperature.
  4. Components shall be rated to a minimum installation temperature of -40°F (-40°C), and maximum pipe temperature of 482°F (250°C).

For detailed product specifications, please refer to the product datasheet.